Siemens MindConnect Nano Getting Started page 85

Getting connected to mindsphere
Hide thumbs Also See for MindConnect Nano:
Table of Contents

Advertisement

EMC
Interference immunity against high-frequency electromagnetic fields
Interference immunity against high
frequency radiation
Interference immunity to cable-borne interference
Interference immunity on supply
cables
Interference immunity on signal
cables >30m
Interference immunity on signal
cables < 30m
Interference immunity against voltage surge
Asymmetric interference
Symmetric interference
Interference immunity to magnetic fields
Interference immunity to magnetic
fields at 50 Hz
Emission of conducted and non-conducted interference
Emission of conducted and non-
conducted interference
Degree and class of protection
IP (at the front)
Standards, approvals, certificates
Approval
CE mark
UL approval
cULus
KC approval
EMC
Ambient conditions
Ambient temperature during operation
Ambient temperature during
operation
Getting Connected to MindSphere
Getting Started, 05/2018
10 V/m for 80 - 1000 MHz, 80% AM acc. to IEC 61000-4-3;
·
3 V/m for 1.4 - 2 GHz, 80% AM acc. to IEC 61000-4-3;
·
1 V/m for 2 - 2.7 GHz, 80% AM acc. to IEC 61000-4-3;
·
10 V for 150 kHz - 80 MHz, 80% AM acc. to IEC 61000-4-6;
·
±2 kV acc. to IEC 61000-4-4, burst;
·
±1 kV acc. to IEC 61000-4-5, surge symmetric;
·
±2 kV acc. to IEC 61000-4-5, surge asymmetric;
·
±2 kV acc. to IEC 61000-4-5, surge, length > 30 m
±2 kV in accordance with IEC 61000-4-4, burst, length > 30 m
±2 kV acc. to IEC 61000-4-5, surge asymmetric
±1 kV acc. to IEC 61000-4-5, surge symmetric
100 A/m; to IEC 61000-4-8
EN 61000-6-4:2007 +A1:2011
IP20
CE (industry), UL, cULus
Yes
Yes
Yes
Yes
CE
·
EN 61000-6-4:2007 +A1:2011
·
EN 61000-6-2:2005
·
EN 61000-6-3:2007 +A1:2011
·
EN 61000-6-1:2007
·
0 °C to 50 °C
A.3 Technical specifications of MindConnect IoT2040
Appendix