ALERT – Variable Simulation
Description:
One or more of the device variables are being simulated.
Corrective Action:
Check the simulation settings for the variables.
Timestamps:
Start: Set when one of the device variables is put into simulation mode.
Stop: Set when all of the devices variables are put into normal mode.

ALERT - Field Device Cutoff Occurred

Description:
The Field Device Cutoff function is enabled and the direct power voltage dropped below this
setting, causing the field device power to be cutoff.
Corrective Action:
Ensure the direct power voltage is a high enough voltage.
Timestamps:
Start: Set when the field device cutoff occurs.
Stop: Set when the field device cutoff ends (by having a direct power voltage high enough).

ALERT - Low Battery

Description:
The VECTOR V1100 is configured to use an external battery, and the battery voltage has
dropped below the Battery Low Voltage parameter, or the calculated remaining battery life is
under 25 days remaining.
Corrective Action:
Replace the external battery.
Timestamps:
Start: Set when the external battery voltage or remaining life calculation passes the low
battery threshold.
Stop: Set when the external battery voltage is above the low battery threshold or you clear the
battery counters.