Automatic Burst Mode Configuration; Factory Reset - GE Masoneilan VECTOR V1100 Instruction Manual

Wirelesshart adapter
Table of Contents

Advertisement

GE Oil & Gas

Automatic Burst Mode Configuration

When this is enabled, the VECTOR V1100 automatically configures burst messages for VECTOR
V1100 itself and all of the connected sub-devices.
The Automatic Burst Mode Configuration setting can be set from within the DD, and allows
you to select several different fixed update rates (8 seconds, 16 seconds, 30 seconds, 1
minute, 2 minutes, 5 minutes, 10 minutes) at which all of the burst messages are published to
the wireless HART gateway.
If this mode is disabled, burst mode can be configured manually using the DD.

Factory Reset

Executing the factory reset resets the following VECTOR V1100 parameters and causes the
VECTOR V1100 to reset (Table 5). The software controlled factory reset can be initiated by
means of the HART Device Description (DD).
VECTOR V1100 Parameter
Adapter Power Mode
Field Device Power Control
Field Device Turn On Time
Field Device Idle Time
Field Device Cutoff Enable
Field Device Cutoff Voltage
Battery Low Voltage
Battery Critical Voltage
Battery Capacity
HART Network ID
HART Join Mode
Radio Output Power
If the Automatic Burst Mode Configuration setting is set, this
NOTE
overrides any manual configuration of the burst mode settings. If
any manual burst mode settings are configured, Automatic Burst
Mode is automatically turned off.
Table 5 HART Dynamic Variables Defaults
HART Join Key
Default Value
Loop Powered - 1.0 V
Off
10.0 seconds
60.0 seconds
Disabled
18.0 V
20.0 V
18.0 V
10000 mAh
1229
44555354 4E455457 4F524B53 524F434B (hex)
Don't Join
+10dBm
28
VECTOR V1100 Wireless Adapter