Loop cables

There is a maximum limit
of 2Km loop cable usage
allowed per loop circuit.
This maximum limit is the
sum of the cable used on
main loop circuit, spurs
off main loop circuit, plus
cable runs to all input
/ output lines off loop
powered interface units
installed on the same loop.
There is a further
maximum limit of 100m
cable run allowed per
input/output line off loop
powered interface unit.
The device loop cable carries both data
and power, therefore its selection is
important. Note the following:
In countries where the European
EMC directive is in force, only EMC
Compliant cables are to be used.
The loop cable usage must not
exceed 2Km. This includes the cable
used on main loop and spur circuits.
Single pair cable must be used. It is
NOT permissible to run mixed loops
or outgoing and return pairs in a
multi core cable, due to inadequate
separation and possible electrical
interference problems.
Each core of the loop cable must be
1.5mm
cross section area.
2
the cable screen must be capable of
being earthed at each system device
(outstation).
Red is the preferred cover sheath for
fi re applications.
The specifi ed loop circuit cables are
also suitable for wiring master alarm,
auxiliary relay, input/output lines and
mains supply.
www.acornfiresecurity.com

Enhanced loop cables

Approved cables for loop wiring
(EMC Compliant)
Draka Firetuf FT120 Enhanced -
FTPLUS2EH1.5RD
(formally Firetuf FT Plus)
Datwyler Pyrofi l Enhanced
Mineral insulated cable (MICC) to
BS6207:Part 1
Prysmian (formally Pirelli)

Standard loop cables

Approved cables for loop wiring
(EMC Compliant)
AEI Cables FIRETEC *
Alcatel cable PYROLON E *
distributed by Winstonlead
BICC Pyrotenax FLAMESIL FRC *
Cavicel SpA FIRECEL SR 114H *
distributed by Cables Britain
Datwyler Pyrofi l Standard *
(previously LIFELINE)
Draka Firetuf EMC Standard 1.5mm
FTEMC2EH1.5RDR
Draka Firetuf FTES2EH1.5 (previously
FTZ2E1.5 FIRETUF OHLS *) fi re
resistant data cable
Huber & Suhner RADOX FR *
Prysmian (formally Pirelli)
FP200 FLEX *
Prysmian (formally Pirelli)
FP200 GOLD *
Raydex CDT FG950 *
2.5mm² Loop cable (2.5Km loop)
For cables marked with an * see note on
the next page.
www.acornfiresecurity.com
Vigilon fire system
FP PLUS *
The cable reference for
a 2.5mm
loop cable is
2
similar to 1.5mm
2
for example the cable
referece for a Draka Firetuf
1.5mm
is FTPLUS2EH1.5
2
and for a 2.5mm
it is
2
FTPLUS2EH2.5, consult
cable supplier.
2
cable,
9