Honeywell Gent Vigilon Installation Instructions Manual page 11

Panel based fire detection and alarm system
Table of Contents

Advertisement

Belden TR No. 89729
(Tefl on jacketed)
1.2Km maximum Panel to Panel or
Panel to Network node cable distance
2 twisted pairs
Each pair individually screened
24AWG (7 strands x 32 AWG)
Capacitance between conductors
39.4pF/m at 1kHz
Capacitance - conductor to screen
72.2pF/m at 1kHz
Temperature range up to 200
Datwyler PYROFIL 8750-U/R*
1.2Km maximum Panel to Panel or
Panel to Network node cable distance
4 cores
each core having 1.5mm
section area
Delta Crompton Firetuf FDZ1000*
1.2Km maximum Panel to Panel or
Panel to Network node cable distance
3 cores
Doncaster Cables Firesure Plus*
1.2Km maximum Panel to Panel or
Panel to Network node cable distance
4 Cores (2- pair plus earth)
each core having 1.5mm
section area
Huber & Schner Radox series FR
communication cable*
1.2Km maximum Panel to Panel or
Panel to Network node cable distance
3 cores twisted triad screened
1.5mm
(7/0.42 stranded)
2
conductors
Nominal impedance 200 ohms
(1KHz)
Capacitance - conductors 110pF/m
(1KHz)
Capacitance - screen to core
210pF/m (1KHz)
Fire resistance tested to BS6387
category CWZ and IEC 331.
www.acornfiresecurity.com
Prysmian (formally Pirelli)
FP200 Flex*
800m maximum Panel to Panel or
Panel to Network node cable distance
Prysmian (formally Pirelli)
FP200 Gold*
1.2Km maximum Panel to Panel or
Panel to Network node cable distance
C
o
Prysmian (formally Pirelli)
FP 400 Armoured
cross
800m maximum Panel to Panel or
2
Panel to Network node cable distance
cross
2
www.acornfiresecurity.com
Vigilon fire system
3 Cores, each having 1.5mm
section area
3 Cores
each core having 1.5mm
section area
4 Cores, each stranded 1.5mm
cross section area
cross
2
cross
2
2
11