Cable termination on enclosure

CABLE TERMINATION
GLAND
GLAND
The wire length between the cable termination and point of connection must be as
short as possible. Cable earth drain wire, where applicable, must be connected to the
nearest earth point.
Terminate each cable at the dedicated entry point on the enclosure, using the cable
manufacturers recommended techniques.
Where cables are not required to be connected to terminals then leave 400mm tail
wire length (unless otherwise specifi ed) and mark each core identifying its fi nal point
of connection. Where the cable is required to be connected, ensure it is secured to the
respective terminal.

Wiring tests

Don't undertake high voltage insulation tests WITH THE CABLES
CONNECTED to the panel and system device terminals. Such a test
may damage the electronics circuitry in loop devices and at the
panel.
Mains & battery supply cables
The mains and battery supply cables must be installed to the stage to facilitate the
power up for commissioning, which is carried out by the Servicing organisation.
Where mains cable is to remain disconnected, its tail ends must be
insulated to prevent dangerous conditions arising in the event of
accidental switching On of the mains supply.
www.acornfiresecurity.com
MICC
MICC CABLE
MICC CABLE
ZINC PLATED
ZINC PLATED
LOCK WASHER
LOCK WASHER
BRASS
BRASS
LOCKNUT
LOCKNUT
PANEL
enclosure
Earth
point
BOARD
BOARD
TERMINALS
TERMINALS
www.acornfiresecurity.com
Softskin (Fire Tuf)
CABLE TERMINATION
EARTH
DRAIN
Softskin Cable
WIRE
Should not
be more than
50mm long
and must be
sleeved
Vigilon fire system