Honeywell Gent Vigilon Installation Instructions Manual page 17

Panel based fire detection and alarm system
Table of Contents

Advertisement

Plug in Card slots
MCC / LCC -P1
IOC / N/W -P2
Loop 1 - P3
Loop 2 - P4
Loop 3 - P5
Loop 4 - P6
Loop 5#, IOC / N/W-P7
Loop 6#, IOC / N/W -P8
Clean contacts
Auxiliary relays
Aux relay 1
Aux relay 2 2 set of change over contacts confi gured to operate immediately on
Master alarm circuits
voltage and current,
protection fuses
RS232 and RS485
connections
Display
Internal sounder
Indicators
Controls (with door
closed) Access level 1
Controls (with door
open)Access level 2a
www.acornfiresecurity.com
Master Control card - supplied
Input Output card / Network card
Loop card - supplied
Loop card option
Loop card option
Loop card option
Loop card#, Input Output card or Network card
Loop card#, Input Output card or Network card
# - for VIG1-72 only
1 set of voltage free change over contacts rated 1A @ 24Vdc, active
with master alarms
Voltage-free contacts rated 1A @ 24Vdc,
2 sets of change over contacts confi gured to operate immediately on
a Fire event. The relay is normally de-energised
a Fault event. The relay is normally energised
The relays can be re-confi gured to operate with Fire, Fault or
Disablement event, with a maximum delay of up to 10 minutes and
can operate in a normally energised or de-energised state.
2 - (24 volts nominal)
400 mA max per circuit
MA1 - fuse 1A FS1
MA2 - fuse 1A FS2
(20 x 5mm) on Terminal card.
The panel will require an optional standard IO Card to facilitate
RS232 for connections for domain bridging and remote printer. The
maximum cable length allowed for RS232 is 15m.
The panel has an RS485 port to accept the Repeat Indicator panels.
The Commissioning tool can be connected to the panel via the
USB port on the Master Control Card.
Display - 8 lines by 40 character per line, back-lit, (Black characters
on green background, liquid crystal display)
Announces Fire & Fault events, plus give key-press confi rmation
beep.
Fire (red) 32, Zones (red) hidden till lit, Verify (amber),
FARE Active (red), FARE Fault/Dis (amber), Power (green), Fault
(amber), Disablement (amber), System fault (amber), Power fault
(amber), Sounder (amber), Test (amber) and Delay (amber)
Next and Previous buttons operable during Fire condition only
Sound Alarms, Silence Alarms, Reset, Cancel Buzzer, Verify, F1-F4
keys, Menu On/Off key, QWERTY key board, U1-U4 keys available if
confi gured to perform site specifi c actions by triggering of command
builds 251, 252, 253 and 254.
www.acornfiresecurity.com
Vigilon fire system
17