Technical data

Technical data

Control panel

Standard
Approval
Panel dimensions in mm
with outer door
Panel weight
VIG1-24
VIG1-72
Battery box#
# with 4 batteries
# with 8 batteries
Storage temperature
Operating temperature
Relative Humidity
Emission
Immunity
Ingress Protection
Colour
Loops
Network
RS232 and RS485
connections
Devices per loop
Device labels
16
www.acornfiresecurity.com
Designed to EN54-2:1997 + A1:2006 (and include optional clauses
7.8, 7.9, 7.9.1, 7.10, 7.10.1, 7.11, 7.12.3, 8.3, 9.5 and 10)
LPCB approved
height 543 x width 406 x depth 172
10.2Kg approximately + 2 batteries
12V 21Ah battery - weight 6Kg each
10.2Kg
7.2Kg
31.2Kg
55.2Kg
-10ºC to +55ºC
-5ºC to +40ºC
up to 90% (Non condensing) Temperature +5ºC to +40°C
BS EN 6100-6-3 : 2001 Residential, Commercial & Light Industry
Class B limits
BS EN50130-4 : 1996 Alarm systems: Electromagnetic compatibility
Product family standard: Immunity requirements for components of
fi re, intruder and social alarm systems
IP30
Door: Grey (Pantone 422) Backbox: Graphite Grey (RAL 7024)
The panel is supplied with a loop card for 1 loop circuit. It can
support up to 4/6 Loop circuits, using optional loop cards.
Two types of network cards are available for secure network
connection:
Fibre Optics - 2Km maximum
Copper (RS485) - 1.2Km maximum
The panel will require an optional IO Card to facilitate RS232 for
connections for domain bridging and remote printer. The maximum
cable length allowed for RS232 is 15m.
The panel has an RS485 port to accept the Repeat Indicator panels.
The Commissioning tool can be connected to the panel via the
USB port on the Master Control Card.
A maximum of 200 addressable devices per loop circuit.
Each device can be given a
32 character label for identifi cation. Each MCP is restricted to
28 character label.