Power supply

Standard
Mains supply voltage and
fuses
Nominal supply voltage for
master alarm circuits
Battery circuit(s)
Battery current with mains
disconnected
Light indications
PSU Fuses
44V supply
Battery charge circuit 1
Battery charge circuit 2
Storage temperature
Operating temperature
Relative Humidity
Indicators
Battery Charging current
EN54 Part 4 data
Hazardous voltages may still be present even when the indicators
are extinguished.
www.acornfiresecurity.com
Designed to EN54-4 : 1997 + A1:2002 and A2:2006
230V -15% +10% 50Hz/60Hz
protected by: FS3 T3.15AH250V Ceramic (20 x 5 mm) on PSU
Input current - 1.4A
24V +1V, -4V
Terminals to connect to internally or externally housed
batteries. Batteries reach fully charged state in 72Hr for
VIG1-24 and VIG1-72.
VIG1-24 - 6.2A max.
VIG1-72 - 6.2A max. over two battery sets
To show the status of PSU
Mains
FS6 T3.15A Ceramic
FS2 F3.15A Glass
FS1 F10A Ceramic for VIG1-72 only
FS7 F6.3A Ceramic Quick Blow for VIG1-24 only
FS3 F10A Ceramic for VIG1-72 only
All fuses 20mm x 5mm size
-10ºC to +55ºC
-5ºC to +40ºC
up to 90% (Non condensing) Temperature +5ºC to +45°C
LD1 - LD5 indicate RAM, ROM and EPROM status, error,
checksum and communication
1 x 2.4A nominal for VIG1-24
2 x 3.6A nominal for VIG1-72
VIG1-24
I min
-> 780uA
I max a* -
max quiescent loop current
I max b -
max alarm loop current
Ri max
-> 0.9R
UVLO
-> 20.7V ± 0.4V
VIG1-72
I min
-> 780uA
I max a* -
max quiescent loop current
I max b -
max alarm loop current
Ri max
-> 1.25R
UVLO
-> 20.7V ± 0.4V
*max a - Max loop current
27mA x 6 = 162mA quiescent for VIG1-72 panel
27mA x 4 = 108mA quiescent for VIG1-24 panel
www.acornfiresecurity.com
Vigilon fire system
-> 108mA @ 43.5V
-> 3.15A @ 46.4V
-> 162mA @ 43.5V
-> 3.15A @ 46.4V
19