Network Cables; Enhanced Network Cables; Standard Network Cables - Honeywell Gent Vigilon Installation Instructions Manual

Panel based fire detection and alarm system
Table of Contents

Advertisement

Network cables

The cables marked * utilise
laminated aluminium tape with a
tinned drain wire for electrostatic
screening. Under certain
environmental conditions galvanic
action may take place between
the aluminium and the drain wire.
This will severely degrade EMC
performance as the foil to drain wire
impedance will increase. Armoured
variants of these can also be used
for wiring a loop circuit.
Network cables

Enhanced Network cables

Approved cables for network wiring
(EMC Compliant)
Draka Firetuf FT120 Enhanced
FTPLUS3EH1.5
(Previously Firetuf FT Plus)
1.2Km maximum Panel to Panel or
Panel to Network node cable distance
3 Cores, each having 1.5mm
section area
Fireshield Enhanced FSN G2000
1.2Km maximum Panel to Panel or
Panel to Network node cable distance
3 Cores (1 pair + 1) and earth
each core having 1mm
section area
Mineral insulated copper cable
800m maximum Panel to Panel or
Panel to Network node cable distance.
BS6207: Part 1
3 parallel cores
having continuous metal sheath
encapsulating
each core having 1.5mm
section area
a red cover sheath (preferred for
alarm applications)
10
www.acornfiresecurity.com

Standard Network cables

Approved cables for network wiring
(EMC Compliant)
cross
2
cross
2
cross
2
Standard network cables continued on
the next page.
www.acornfiresecurity.com
Prysmian (formally Pirelli) FP Plus*
1.2Km maximum Panel to Panel or
Panel to Network node cable distance
3 Cores each having 1.5mm
section area
Belden Armoured equivalent
This cable being a two pair cable
to BS5308:Part 1 (type 2) 0.5mm
(16/0.2mm).
600m maximum Panel to Panel or
Panel to Network node cable distance.
Belden No 9729 (UL Style 2493)
1.2Km maximum Panel to Panel or
Panel to Network node cable distance
2 twisted pairs
Each pair individually screened
24AWG (7 strands x 32 AWG)
Capacitance between conductors
39.4pF/m at 1kHz
Capacitance conductor to screen
72.2pF/m at 1kHz
Temperature range -30
Belden No. 9842 EIA RS485
Applications, O/A Beldfoil® Braid
1.2Km maximum Panel to Panel or
Panel to Network node cable distance
Must have following characteristics:
2 twisted pairs
24AWG (7 strands x 32 AWG)
conductors
Characteristic impedance -
120ohms
Capacitance between conductors -
42pF/m at 1kHz
Capacitance conductor to screen -
75.5pF/m at 1kHz
cross
2
2
C to +60
C
o
o

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents