Section 7: Power Supply Calculations; Overview; Calculating The Ac Branch Circuit; Calculating The System Current Draw - Honeywell NOTIFIER FireWarden-100-2 Instruction Manual

Fire alarm control panel
Table of Contents

Advertisement

Section 7: Power Supply Calculations

7.1 Overview

This section contains instructions and tables for calculating power supply currents in alarm and
standby conditions. This is a four-step process, consisting of the following:
1.
2.
3.
4.

7.2 Calculating the AC Branch Circuit

The control panel requires connection to a separate, dedicated AC branch circuit, which must be
labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed
of the protected premises. No other non-fire alarm equipment may be powered from the fire alarm
branch circuit. The branch circuit wire must run continuously, without any disconnect devices,
from the power source to the control panel. Overcurrent protection for this circuit must comply
with Article 760 of the National Electrical Codes as well as local codes. Use 14 AWG (2.00 mm
wire with 600 volt insulation for this branch circuit.
Use Table 7.1 , to determine the total amount of current, in AC amperes (A), that must be supplied
to the system.
Device Type
NFW2-100
NFW2-100E
CHG-75
CHG-120

7.3 Calculating the System Current Draw

7.3.1 Overview
The control panel must be able to power all internal and external devices continuously during the
non-fire alarm condition. To calculate the non-fire alarm load on the system power supply when
primary power is applied, use Calculation Column 1 in Table 7.3 on page 160. The control panel
must support a larger load current during a fire alarm condition. To calculate the fire alarm load on
the power supply, use Calculation Column 2 in Table 7.3 on page 160. The secondary power
source (batteries) must be able to power the system during a primary power loss. To calculate the
non-fire alarm load on the secondary power source, use Calculation Column 3 in Table 7.3 on page
160.
158
Calculating the total amount of AC branch circuit current required to operate the system
Calculating the power supply load current for non-fire and fire alarm conditions and
calculating the secondary (battery) load
Calculating the size of batteries required to support the system if an AC power loss occurs
Selecting the proper batteries for your system
Table 7.1 AC Branch Circuit Requirements
Number of
Devices
or
1
[
]
[
]
[
]
Sum Column for AC Branch Current Required
Current Draw
(AC amps)
3.00
X
or
1.50
X
2.05
X
2.00
X
[
]
FireWarden 100-2/E — P/N 52778:A 11/04/2005
2
Total Current
per Device
=
=
=
=
=
)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier firewarden-100-2e

Table of Contents