Fire alarm and suppression system

Component to be inspected
Full system functional check

Generator (if applicable)

Component to be inspected
Generator
*These are typical frequencies. See the documentation for the installed component for the recommended schedule.
Task
Inspect and perform a functional
check of the system.
Inspect and test fire panel
battery backup system.
Inspect and test VESDA power
supply.
Inspect the VESDA pipe
network.
Inspect the VESDA filter.
Conduct a VESDA pipe integrity
smoke test.
Check the VESDA pipe flow.
Clean the VESDA sampling
points.
Flush the VESDA pipe network.
VESDA system air
sampling/smoke test
Suppression system test
Fire-pull visual and operational
inspection
Fire strobe and horn visual and
operational inspection
Task
Visual inspection of the generator Quarterly
Oil change
Oil filter change
Oil analysis
Fuel filter change
Coolant freeze point and
inhibition check each time the
generator is viewed
Frequency
Capable Party
As required by
Licensed fire safety
local code
contractor
Bi-annually
Licensed fire safety
contractor
Quarterly
Licensed fire safety
contractor
Bi-annually
Licensed fire safety
contractor
Annually
Certified facilities
personnel
Annually
Licensed fire safety
contractor
Annually
Licensed fire safety
contractor
Every 2 years
Licensed fire safety
contractor
Every 2 years
Licensed fire safety
contractor
As required by
Licensed fire safety
local code
contractor
As required by
Licensed fire safety
local code
contractor
As required by
Licensed fire safety
local code
contractor
As required by
Licensed fire safety
local code
contractor
Frequency*
Capable Party
HP and certified
facilities personnel
Annually
HP
Annually
HP
Annually
HP
Annually
HP
HP
Periodic maintenance 67