Regulatory compliance notices

HP POD 40c G2 regulatory compliance

The HP POD 40c G2 complies with the following regulatory standards.
Standard
Certification level
ETL "Listed"
UL 60950
ETL "Classified"
NFPA 70
Designed to Comply
NFPA 72
With
NFPA 2001 Designed to Comply
With
Designed to Comply
IBC 2009
With

Safety and NEC compliance

The HP POD 40c G2 is certified to UL 69050-1/IEC 60950-22 as a Modular Data Center Information
Technology Product and classified according to the National Electric Code NFPA 70 in accordance with
NEC (NA) and IEC (EMEA and APJ). Relevant parts of UL1995 are applied to the air handling features of the
product. For more information, see "HP POD 40c G2 regulatory compliance (on page 74)."
The HP POD 40c G2 is not suitable for long-term human occupancy. The HP POD 40c G2 has service access
areas for periodic maintenance and service. These areas must be used only by owner-authorized personnel
who are trained in the maintenance and service of the HP POD 40c G2 components.
IMPORTANT:
and to review site-specific location guidelines. If needed, obtain any necessary permits.
Additional considerations for safety and NEC compliance are as follows:
The HP POD 40c G2 is listed as an Information Technology Equipment Product to UL 60950.
The HP POD 40c G2 is evaluated as a "non-inhabitable product" that provides "service access" areas
for customer-authorized, qualified, and trained service personnel.
The electrical connections of the HP POD 40c G2 are evaluated as feeder connections for connection
to an existing facility, and are not suitable as "service entrance" for connection to the utility.
The HP POD 40c G2 is designed for stationary installation outdoors in a Pollution Degree 3
environment, in restricted access locations, with field wiring terminals provided for permanent supply
connections.
Standard title
UL 60950—Standard for Safety Information Technology
Equipment, Part 1: General Requirements, Issue: 2007/03/27,
Edition: 2
UL 60950—Standard for Safety Information Technology
Equipment, Part 22: Equipment to be Installed Outdoors, Issue:
2007/04/23, Edition: 1
NFPA 70—National Electric Code, 2008 Edition, © 2008 National
Fire Protection Association
National Fire Alarm code, 2007 Edition, © 2006 National Fire
Protection Association
NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems,
2008 Edition, © 2008 National Fire Protection Association
2009 International Building Code, © 2010 International Code
Council, Inc.
Before installing the HP POD 40c G2, consult your local AHJ for applicable codes