Spectrum Controls 1769 Series User Manual page 19

6 channel isolated thermocouple/mv input module
Hide thumbs Also See for 1769 Series:
Table of Contents

Advertisement

User's Manual Pub. 0300244-01 Rev. A
Chapter 2: Quick Start for Experienced Users
Ground the shield drain wire at one end only. The preferred location is as
follows.
o
For grounded thermocouples or millivolt sensors, this is at the sensor
end.
For insulated/ungrounded thermocouples, this is at the module end.
o
Contact your sensor manufacturer for additional details.
Refer to Industrial Automation Wiring and Grounding Guidelines, Allen-
Bradley publication 1770-4.1, for additional information.
The terminal connections with CJC sensors are shown below:
Step 4: Configure the module.
The configuration file is typically modified using the programming software compatible
with your controller. It can also be modified through the control program, if supported
by the controller. See Channel Configuration on page 4-3 for more information.
Step 5: Go through the startup
procedure.
1) Apply power to the controller system.
2) Download your program, which contains the thermocouple module
configuration settings, to the controller.
Reference
Chapter 4
(Module Data, Status, and
Channel Configuration)
Reference
Chapter 5(Diagnostics and
Troubleshooting)
2-5