2.2.3 Connecting outputs

LOGO! 230R, LOGO! 230RC and LOGO! 24R
The outputs of LOGO! 230R, LOGO! 230RC and LOGO! 24R are relays.
The contacts of the relays are isolated from the power supply and the in-
puts.
Requirements for the relay outputs
You can connect different loads to the outputs, such as lamps, fluorescent
tubes, motors, contactors, etc. The loads connected to LOGO! 230R/RC
and LOGO! 24R must have the following properties:
S
The maximum switched current depends on the type of load and the
number of operations. You will find more information on this in the
technical specifications.
S
When switched on (Q = 1), the maximum current is 8 amperes for a
non-inductive load and 2 amperes for an inductive load.
Connecting
You connect the load to LOGO! 230 R/RC and LOGO! 24R as follows:
L1
Protection with auto-
matic circuit breaker
(max. 16 A, B16),
e.g. power circuit
breaker 5SX2 116-6
8
N/M
Load
LOGO! manual