Technical data
Criterion
Electromagnetic compatibility (EMC)
Electrostatic
discharge
Electromagnetic fields
Interference suppression
Burst pulses
Energy carriers single
pulse (surge)
(applies only to
LOGO! 230R and
LOGO! 230RC)
Information on IEC/VDE safety
Measurement of clearance
and creepage distance
Insulation strength
Technical data on LOGO! 230R and LOGO! 230RC
Power supply
Input voltage
Rated value
Permissible range
VDE 0631:
IEC 1131:
Permissible mains frequency
Power consumption from
115/120 V AC
230/240 V AC
Voltage failure bridging
115/120 V AC
230/240 V AC
106
Complies with
IEC 801-2
Severity 3
IEC 801-3
EN 55011
IEC 801-4
Severity 3
IEC 801-5
Severity 2
IEC 664, IEC 1131,
EN 50178 11/94
UL 508, CSA C22.2
No 142
Also VDE 0631 for
LOGO! 230R/RC
IEC 1131
Values
8 kV air discharge
6 kV contact discharge
Field strength 10V / m
Limit class B group 1
2 kV
(supply lines)
2 kV (signal lines)
0.5 kV (supply lines) sym-
metrical
1 kV (supply lines) asym-
metrical
Fulfilled
Fulfilled
115 V/120 V/230 V/240 V AC
85 V to 250 V AC
85 V to 265 V AC
47 to 63 vHz
Typically 40 mA
Typically 26 mA
Typically 10 ms
Typically 20 ms
LOGO! manual
EWA 4NEB 712 6006-02