6 Technical data
General technical data
Criterion
Dimensions W×H×D
in mm
Weight
Installation
Ambient climatic conditions
Ambient temperature
Horizontal installation
Vertical installation
Storage/transport
Relative humidity
Atmospheric pressure
Pollutants
Ambient mechanical conditions
Protection type
Vibrations
Shock
Drop
Free fall (packaged)
*
IEC 68 includes VDE 0631
LOGO! manual
EWA 4NEB 712 6006-02
Complies with
Cold: IEC 68-2-1
Heat:
*
IEC 68-2-2
IEC 68-2-30
IEC 68-2-42
IEC 68-2-43
IEC 68-2-6
IEC 68-2-27
IEC 68-2-31
IEC 68-2-32
Values
72 x 90 x 55
with installation mechanism:
72 x 90 x 59
approx. 190 g
on 35 mm DIN rail
Width of 4 modules
0 to 55 °C
°
0 to 55 °C
*40 °C to + 70 °C
From 5 to 95%
no condensation
From 795 to 1080 hPa
3
3
SO
10 cm
/m
, 4 days
s
3
3
H
S 1 cm
/m
, 4 days
s
IP 20
10 to 57 Hz (constant ampli-
tude 0.15 mm)
57 to 150 Hz (constant ac-
celeration 2 g)
18 shocks
(half-sine 15g/11ms)
Drop height 50 mm
1 m
105