Siemens SIMATIC NET CP 343-2 Manual page 66

Interface master
Table of Contents

Advertisement

5 Using the Command Interface
5.2.5
Store_Actual_Parameters
Meaning
With this call, the configured parameters stored on the EEPROM are overwritten
with the current, permanently stored (actual) parameters; in other words, the
parameters of all the AS-i slaves are configured.
For AS-i slaves that comply with the AS-i slave standard profile 7.4, the AS-i
master manages the AS-i slave parameter assignment itself. The configured
parameters for these AS-i slaves always have the value F
Structure of the Job Data in the Send Buffer
Byte
0
66
H
Meaning
Command number: 04
H
CP 343−2 / CP 343−2 P AS−Interface Master
.
Release 08/2008
C79000−G8976−C149−04