1 Technical Description
1.9

Addressing the CP 343-2 in the S7 Automation System

The CP 343-2 can be addressed by the PLC like an analog module with 16 input
bytes and 16 output bytes. The CP occupies 16 input bytes and 16 output bytes in
the I/O address space of the S7 automation system (analog area on the AS).
Of the 16 bytes I/O address area of the CP 343-2, 31 x 4 bits are used for the
binary data of the AS-i standard slaves or A slaves. The remaining four bits are
reserved for later applications.
The base address n of this address area is fixed as follows by the slot of the
CP 343-2.
Rack 0
Module
PS
Slot number
1
Base address
1
Rack 1
Module
Slot number
Base address
Rack 2
Module
Slot number
Base address
Rack 3
Module
Slot number
Base address
Note
In most CPUs (for example, the CPU 315-2DP, 318), the slot-oriented addressing
can be modified with STEP 7 configuration (HW Config).
In particular, with the freely configurable CPUs, it is possible to address the
standard AS-i slaves or the A/B slaves with A addresses from the extended
address area via the process image of the inputs and outputs.
24
CPU IM
CP
CP
2
3
4
5
2
3
256
272
IM
CP
CP
3
4
5
384
400
IM
CP
CP
3
4
5
512
528
IM
CP
CP
3
4
5
640
656
CP
CP
CP
CP
6
7
8
9
288
304
320
336
CP
CP
CP
CP
6
7
8
9
416
432
448
464
CP
CP
CP
CP
6
7
8
9
544
560
576
592
CP
CP
CP
CP
6
7
8
9
672
688
704
720
CP 343−2 / CP 343−2 P AS−Interface Master
C79000−G8976−C149−04
CP
CP
10
11
352
368
CP
CP
10
11
480
496
CP
CP
10
11
608
624
CP
CP
10
11
736
752
Release 08/2008

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SIMATIC NET CP 343-2 and is the answer not in the manual?

This manual is also suitable for:

Simatic net cp 343-2 p asSimatic net cp 343-2 p6gk7 343-2ah01-0xa06gk7 343-2ah11-0xa0

Table of Contents

Save PDF