Siemens SIMATIC NET CP 343-2 Manual page 113

Interface master
Table of Contents

Advertisement

Table 10-1 , continued
Error
The CER display flickers, in other
words a configured slave is lost
sporadically.
sporadically.
The CP 343-2 does not switch
from the configuration mode to
from the configuration mode to
the protected mode.
The CP 343-2 does not switch
from the protected mode to the
from the protected mode to the
configuration mode.
After failure of an AS-i slave, the
"AUP" display remains off.
Automatic address programming
is unsuccessful although the
"AUP" display is lit.
CP 343−2 / CP 343−2 P AS−Interface Master
Release 08/2008
C79000−G8976−C149−04
7 Dealing with Problems / Error Displays
Possible Cause
Bad contact
Interference on the AS-i cable.
The PLC is in the "RUN" mode.
The SET button was not pressed
long enough.
An AS-i slave with address 0 is
connected to the AS-i cable.
The CP 343-2 cannot change to
the protected mode as long as
this slave exists.
The PLC is in the "RUN" mode.
The SET button was not pressed
long enough.
The CP 343-2 is in the configura-
tion mode.
More than one AS-i slave has fai-
led.
The CP 343-2 has not detected
configured AS-i slaves.
The AUTO_ADDRESS_ENABLE
flag is not set.
The configuration data (I/O confi-
guration, ID code) of the replaced
AS-i slave do not match the va-
lues of the original slave.
The replaced AS-i slave does not
have the address "ZERO".
Remedy
Check the electrical connections
of the AS-i slaves.
Check the correct grounding of
the CP 343-2 module and check
the AS-i cable. Check that the
shield of the AS-i power supply
unit is connected correctly.
Switch the PLC to "STOP".
Press the SET button for at least
0.5 seconds.
Remove the AS-i slave with ad-
dress 0.
Switch the PLC to "STOP".
Press the SET button for at least
0.5 seconds.
"Automatic Programming" is not
possible in the configuration
mode.
Program the address of the new
AS-i slave with the address pro-
grammer or using the command
interface of the CP 343-2.
Check the AS-i cable.
If "APF" is displayed at the same
time, check the power supply on
the AS-i cable.
If more than one slave is defec-
tive, program the address on the
replaced slaves using the addres-
sing unit.
Remove the unconfigured AS-i
slaves from the AS-i cable.
Set the bit with the appropriate
FC calls
Check whether the correct "repla-
cement slave" was used.
Compare the information from the
manufacturer about configuration
data.
If you want to replace the original
slave with a different type, assign
the address with the addressing
unit and reconfigure the CP 343-2
module (with the SET button).
Set the address of the replaced
slave with the addressing unit.
113