Structure and function
3

Function

3.1.4 Scope of delivery

3.1.5 Details for ordering

3.2 Function

3.2.1 Diagnosis levels

Diagnosis level Meaning
Normal
No faults present.
The radio gateway is fully functional.
Battery low
The battery voltage is too low.
Battery pack replacement recommended.
Battery empty
The radio gateway is only being supplied
with power via the detector line.
The battery is completely discharged or
missing.
Battery pack replacement necessary.
Fault
The radio gateway has only limited
1
functionality.
18 | 62
Building Technologies
Fire Safety
1x radio gateway FDCW241
1x screw for cover
2x cable ties (2.4 x 102 mm) for cable strain relief
Batteries are not included in the scope of delivery. A battery pack is always
needed to commission and operate the radio gateway.
Type
FDCW241
FDCW241
The radio gateway monitors its operation largely autonomously. If a radio gateway
fails, a fault is signaled and displayed on the control unit.
The following diagnosis levels are derived from the various control measurements
in the radio cell:
Normal
Battery low
Battery empty
Fault
This diagnosis level can be indicated together with other diagnosis levels,
1
e.g., with 'Battery low'.
Order number
Designation
S54370-F11-A1
Radio gateway
S54370-F11-A3
Radio gateway (colored)
Measures
None
Connect a new battery pack.
Test the detector line voltage.
Check whether all the radio devices are
logged on.
Replace the radio gateway.
A6V10227639_k_en_--
2016-11-28