Commissioning
6
Commissioning the radio cell
36 | 62
Building Technologies
Fire Safety
13. Connect the radio gateway and the detector line.
Switch the detector line off.
Insert the 'detector line socket strip'.
The radio gateway is now connected to the detector line.
14. Close the radio gateway housing.
15. Read in the radio cell at the control panel.
All the radio devices have now been read in at the fire control panel. Two
addresses are displayed for the radio gateway.
1. Make a note of the sequence of the commissioned radio devices.
2. Use the FXS2061 SWING Tool to back up the network file. The procedure for
backing up the network file is described in more detail in the User Guide
SWING-Tool FXS2061 in the 'Menu bar' chapter.
You will find more information in the 'Changing and expanding the FDnet/C-NET
detector line' chapters of the following documents:
For control panels FC20xx: Document 009052
For control panels FC72x: Document A6V10210416
See also
Replacing the batter pack on the radio gateway [
52]
A6V10227639_k_en_--