7.2 Putting the radio cell into maintenance mode

Building Technologies
Fire Safety
Figure 15: Radio gateway FDCW241
H2
Yellow LED for maintenance mode
S1
Button for maintenance mode
The housing for the radio gateway is open.
The radio gateway is in normal operation.
1. Switch off the relevant zone on the station.
LED (H2) is not flashing.
2. Press and hold button (S1) for at least 2 seconds until LED (H2) flashes.
The radio gateway and its radio cell are in maintenance mode.
LED (H2) flashes at 1-second intervals.
The radio devices can now be logged on.
You will find more information in the 'Changing and expanding the FDnet/C-NET
detector line' chapters of the following documents:
For control panels FC20xx: Document 009052
For control panels FC72x: Document A6V10210416
Maintenance / troubleshooting
Putting the radio cell into maintenance mode