Running Automatic Battery Tests - Eaton BladeUPS User Manual

5 kva to 60 kva (n+1) systems
Hide thumbs Also See for BladeUPS:
Table of Contents

Advertisement

Table 15. Suggested Battery Low Alarm Level Settings
Warning Time
(in Minutes)
NOTE Values are approximate.
5 5 . . 2 2 0 0 R R u u n n n n i i n n g g A A u u t t o o m m a a t t i i c c B B a a t t t t e e r r y y T T e e s s t t s s
NOTE
ESC
Number of EBMs
Installed
1
2
2
3
4
1
2
3
3
4
1
2
4
3
4
1
2
5
3
4
Battery Low Alarm Level (User Setting)
20% Load
1.783
1.776
1.772
1.768
1.805
1.793
1.787
1.781
1.822
1.807
1.789
1.793
1.835
1.818
1.799
1.803
Eaton BladeUPS 5 kVA to 60 kVA (N+1) User's Guide 164201649—Rev 14

Running Automatic Battery Tests

50% Load
100% Load
1.821
1.854
1.811
1.831
1.798
1.818
1.781
1.805
1.848
1.891
1.833
1.859
1.820
1.843
1.803
1.831
1.868
1.918
1.850
1.883
1.836
1.866
1.818
1.850
1.884
1.941
1.863
1.903
1.849
1.883
1.823
1.865