Table 15. Suggested Battery Low Alarm Level Settings
Warning Time
(in Minutes)
NOTE Values are approximate.
5 5 . . 2 2 0 0 R R u u n n n n i i n n g g A A u u t t o o m m a a t t i i c c B B a a t t t t e e r r y y T T e e s s t t s s
NOTE
ESC
Number of EBMs
Installed
1
2
2
3
4
1
2
3
3
4
1
2
4
3
4
1
2
5
3
4
Battery Low Alarm Level (User Setting)
20% Load
1.783
1.776
1.772
1.768
1.805
1.793
1.787
1.781
1.822
1.807
1.789
1.793
1.835
1.818
1.799
1.803
Eaton BladeUPS 5 kVA to 60 kVA (N+1) User's Guide 164201649—Rev 14
Running Automatic Battery Tests
50% Load
100% Load
1.821
1.854
1.811
1.831
1.798
1.818
1.781
1.805
1.848
1.891
1.833
1.859
1.820
1.843
1.803
1.831
1.868
1.918
1.850
1.883
1.836
1.866
1.818
1.850
1.884
1.941
1.863
1.903
1.849
1.883
1.823
1.865
107