Configuring Battery Settings

Set the UPS for the number of EBMs installed, whether to run automatic battery tests, and automatic restart
configuration.

Configuring the UPS for EBMs

To ensure maximum battery runtime, configure the UPS for the correct number of EBMs (see Table 4):
1.
Press any button on the front panel display to activate the menu options, then select SETTINGS, USER
SETTINGS, and NUMBER OF BATTERY STRINGS.
2.
Use the
Table 4. Configuring the UPS for EBMs
All UPS and EBM Cabinets
NOTE
If 0 is selected, no batteries are connected and all battery-related alarms are disabled.
NOTE
The UPS contains one battery string; each EBM contains two battery strings.
3.
Press the
4.
Press the

Running Automatic Battery Tests

Automatic battery tests run approximately every 30 days, unless disabled. During the test, the UPS transfers
to Battery mode and discharges the batteries for 25 seconds under the existing load.
For automatic battery tests to run:
The "Automatic Battery Support Tests" setting must be enabled.
l
The UPS must be in Normal mode, with no active alarms.
l
The batteries must be fully charged.
l
The bypass voltage must be acceptable.
l
No manual battery test was initiated previously in the same charging cycle.
l
or
buttons to select the number of battery strings according to your UPS configuration:
UPS only (internal batteries)
UPS + 1 EBM
UPS + 2 EBMs
UPS + 3 EBMs
UPS + 4 EBMs
button to save the setting.
(
button until the start screen appears.
ESC
NOTE
The "UPS on Battery" notice and the "Battery Low" alarm do not activate during a
battery test.
Eaton 9130 700/3000 VA UPS User's Guide 164201718—Rev 7 www.eaton.com/powerquality
Number of Battery Strings
1 (default)
3
5
7
9