Automatic Battery Test

NOTE
8 8 . . 4 4
A A u u t t o o m m a a t t i i c c B B a a t t t t e e r r y y T T e e s s t t
The Eaton FX Ferrups UPS has a built in automatic battery discharge test feature. When ABM is enabled (by
default) the battery discharge test will run automatically every 90 days. The duration of the battery test can be
modified by changing parameter 93.
93
If custom battery is enabled the battery test will run based on the custom battery test parameter set points
listed below.
72
73
75
52
Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User's Guide P-164000906—Rev 05
[91]
[ENTER]
[PROGRAM]
ABM provides optimum battery performance and lifetime improving total cost of
ownership. ABM will be enabled when the total UPS and EBM battery capacity is less
than or equal to 200Ah. ABM is disabled for UPS and EBM battery capacity exceeding
200 Ah and the UPS internal charger will switch to float charge mode.
AbmTestIntrvl
93 AbmIntrvl 3 mo
TestIntrl
72 TestIntrl 7 d
BatTestToD
73 Test@ 1:00:00
BatTestLen
75 BT Time 60 s
91 Pgm: (Enter in Amp hour of the battery you are using)
3,4,5,6 Months
User
When using custom batteries, the
discharge test interval, the time
User
7 - 180
between discharge tests.
When using custom batteries, the
User
0 - 23:59:00
time of day that the battery discharge
test will start.
When using custom batteries, the
User
60 - 180
test will discharge the batteries for
this amount of time.
Display: 91
BatAmpHrs: 0 AH
ABM Discharge Test
Interval.