Siemens SINAMICS G120 PM240P-2 Installation Manual page 63

Frequency converters
Table of Contents

Advertisement

Table 6- 3
PM240P-2, IP20, Frame Size F, 3-ph. AC 380 V ... 480 V
Article number without filter
Article number with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
Power loss without filter
Power loss with filter
Required cooling air flow
Weight without filter
Weight with filter
Table 6- 4
PM240P-2, IP20, Frame Size F, 3-ph. AC 380 V ... 480 V
Article number without filter
Article number with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
Power loss without filter
Power loss with filter
Required cooling air flow
Weight without filter
Weight with filter
Power Module PM240P-2
Hardware Installation Manual, 06/2020, A5E37800827C AD
6SL3210-1RE31-5UL0
6SL3210-1RE31-5AL0
75 kW
140 A
145 A
55 kW
117 A
110 A
3NE1225-0 / 200 A
200 A
1.95 kW
1.97 kW
153 l/s
58 kg
64 kg
6SL3210-1RE32-5UL0
6SL3210-1RE32-5AL0
132 kW
242 A
250 A
110 kW
218 A
205 A
3NE1331-0 / 350 A
350 A
3.09 kW
3.12 kW
153 l/s
62 kg
66 kg
6SL3210-1RE31-8UL0
6SL3210-1RE31-8AL0
90 kW
172 A
178 A
75 kW
154 A
145 A
3NE1227-0 / 250 A
250 A
2.54 kW
2.56 kW
153 l/s
58 kg
64 kg
Technical data
6.4 400 V converters
6SL3210-1RE32-1UL0
6SL3210-1RE32-1AL0
110 kW
198 A
205 A
90 kW
189 A
178 A
3NE1230-0 / 315 A
300 A
2.36 kW
2.38 kW
153 l/s
62 kg
66 kg
61