6.7
Restrictions for special ambient conditions
Maximum current at low speeds
NOTICE
Overheating the converter due to unsuitable load
Loading the converter with a high output current at the same time as a low output frequency
can cause the current-conducting components in the converter to overheat. Excessively
high temperatures can damage the converter or have a negative impact on the converter
service life.
• Never operate the converter continuously with an output frequency = 0 Hz.
• Only operate the converter in the permissible operating range.
Figure 6-2
● Continuous operation:
Operating state that is permissible for the complete operating time.
● Short-time duty cycle:
Operating state that is permissible for less than 2 % of the operating time.
● Sporadic short-time duty cycle:
Operating state that is permissible for less than 1 % of the operating time.
Power Module PM240P-2
Hardware Installation Manual, 06/2020, A5E37800827C AD
Permissible operating range of the converter
6.7 Restrictions for special ambient conditions
Technical data
69