7. Electrical Engineering

7.1 Wiring terminals instruction
A
B
C
N
Three-phase power supply
7.2 Power supply wiring installation
7.2.1 Outdoor unit power supply wiring
7.2.2 Indoor unit power supply wiring
Note:
 Set refrigerant piping system, signal wires between indoor units and signal wires between outdoor units into one
system.
 Power must unified supply to all indoor units in the one system.
 Please do not put the signal wires and power wires in the same wire tube; keep distance between the two tubes. (Keep
distance above 300mm; when current capacity of power supply less than 10A, and Keep distance above 500mm, when
current capacity of power supply less than 50A).
Make sure to address the outdoor unit which is in combination type.
7.2.3 Electric characteristics
Model
38VF008H117010
38VF010H117010
38VF012H117010
38VF014H117010
38VF016H117010
38VF018H117010
146
Outdoor units
centralized
monitoring
Leakage protector
Manual switch
1
2
3
9
10
11
Outdoor Unit
Hz
Voltage
Min.
Max.
60
208
188
253
60
208
188
253
60
208
188
253
60
208
188
253
60
208
188
253
60
208
188
253
Indoor units
Network
Indoor units
centralized
accounting
communication
contros
Branch box
4
5
6
7
Indoor unit
12
13
14
15
Power Supply
MCA
TOCA
MFA
MSC
36.0
35.0
40
36.0
35.0
40
46.5
49.5
55
54.6
54.4
60
54.6
54.4
60
54.6
54.4
60
Carrier service manual
Outdoor units
communication
8
16
Compressor
OFM
RLA
kW
-
35.5
0.42
-
35.5
0.42
-
35.5+21.1
0.22*2
-
35.5+21.1
0.36×2
-
35.5+21.1
0.36×2
-
35.5+21.1
0.36×2
Installation
FLA
4.4
4.4
2.2*2
3.4×2
3.4×2
3.4×2