R410A DC Inverter Series
4.16 xP9/xH9: Fan module protection (Display on faulty unit, all the ODU in standby)
If the system display three times P9 protection in 60 minutes, the system will stop and display H9 error code.
When the system displays H9 error code, the system can resume only by restarting the machine. At this time,
malfunction should be disposed promptly to avoid further damage.
P9/H9: Fan module protection
The fan module is too hot for bad
heat dissipation or high ambient
temperature
No
Some power wires or signal
wires of fan module are loose
No
The fan motor is blocked or disabled
No
Output voltage between P and
N on fan module is abnormal*
No
Fan module is disabled
Fan module instruction
3
184
Yes
Make sure the fan module working
in the normal temperature range
Yes
Well connect the power wires
and signal wires
Yes
Clear away the block or replace
the fan motor
Yes
Replace the power supply module
Replace the fan module
1
5
4
2
6
P
Carrier service manual
1
Program input port
2
Power supply indicator lamp
3
Fan motor U, V, W output port
4
Fault indicator lamp
5
PCB control signal input port
6
Signal feedback port
* The normal value of output
voltage between P and N on fan
module is DC 310V
Troubleshooting