Carrier X-POWER Series Service Manual page 145

Full dc inverter outdoor unit
Hide thumbs Also See for X-POWER Series:
Table of Contents

Advertisement

Carrier service manual
3. Error code table
Error code
E0
Communication error between outdoor units
E2
Indoor units and master unit communication error
E4
T3 or T4 temperature sensor error
E5
Voltage error
E7
Discharge temperature sensor error
E8
Outdoor unit address error
xH0
Communication error between DSP and the main chip
H1
Communication error between 0537 and main chip
H2
Outdoor unit quantities decreasing malfunction
H3
Outdoor unit quantities increasing malfunction
xH4
There are 3 times P6 protection in 60 minutes
H5
There are 3 times P2 protection in 60 minutes
H6
There are 3 times P4 protection in 100 minutes
H7
Indoor unit quantities decreasing malfunction
H8
High pressure sensor malfunction
H9
There are 3 times P9 protection in 60 minutes
Auxiliary unit error(y=1,2,3,e.g, 1Hd stands for
yHd
auxiliary unit 1 error)
P1
High pressure protection
Low pressure protection
P2
xP3
Compressor over current protection
P4
Discharge temperature sensor protection
P5
Pipe temperature sensor protection
xP6
Inverter module protection
P9
DC Fan protection
PL
The temperature protection of inverter module
C7
3 times of PL protection in 100 minutes
DC compressor module error
xL0
xL1
DC bus low voltage protection
xL2
DC bus high voltage protection
xL3
Reserve
xL4
MCE malfunction/simultaneously/cycle loop
xL5
Zero speed protection
xL6
Reserve
xL7
Voltage protection
Protection of the speed change between a
xL8
moment before and after is >15Hz
Protection of the speed change between
xL9
the setting speed and the actual speed >15Hz
Troubleshooting
Content
R410A DC Inverter Series
Note
Only display on faulty slave unit, all the ODU in
standby
20 minutes after first power on or indoor and
outdoor communication break off over 2
minutes after first power on 20 minutes
x represents for a system, 1 is A system, 2 is B
system.
Only master unit will display
Only master unit will display
Recovery after power on again
Recovery after power on again
Recovery after power on again
Indoor unit quantities decreasing over 3
minutes. Recovery when detected the max.
number of units.
Exhaust pressure ≤0.3Mpa will protect
Recovery after power on again
y represents for a unit which is not No. 0
There are 3 times P2 protection in 60 minutes.
Display H5, can't recover.
x represents for a system, 1 is A system, 2 is B
system.
There are 3 times P6 protection in 100 minutes.
Display H6, can't recover.
x represents the system which it is. There are 3
times P6 protection in 60 minutes.
Display H4, can't recover.
There are 3 times P9 protection in 60 minutes.
Display H9, can't recover.
x represents for a system, 1 is A system, 2 is B
system.
x represents for a system, 1 is A system, 2 is B
system.
x represents for a system, 1 is A system, 2 is B
system.
x represents for a system, 1 is A system, 2 is B
system.
x represents for a system, 1 is A system, 2 is B
system.
x represents for a system, 1 is A system, 2 is B
system.
x represents for a system, 1 is A system, 2 is B
system.
x represents for a system, 1 is A system, 2 is B
system.
x represents for a system, 1 is A system, 2 is B
system.
x represents for a system, 1 is A system, 2 is B
system.
163