7.3.3 Signal wire of centralized control
Signal wire of centralized control
When centralized control is needed, one CCM03 (central controller of indoor unit) can only control the
indoor units which are in the same refrigerant system via the port X Y E of outdoor unit. Outdoor unit
will automatically distribute the address to indoor units without any manual setting. Remote controller
can enquiry and modify every indoor unit address.
The diagram below shows the connection of signal wire in this case:
CCM03
To RS485/RS232
(F1,F2,E)
Converter
CCM02
To RS485/RS232
(F1,F2,E)
query
Page up
Previous
M
Set
Module
Ok
Next
Page down
Converter
Address Lock
Besides, CCM03 can also connect indoor units via the port X Y E of indoor unit. However, one more
group of wire(X Y E between indoor units) is needed; it is more complex and not suggested. Anyway, the
diagram below shows the connection of signal wire in this case:
CCM02
To RS485/RS232
(F1,F2,E)
query
Page up
Previous
M
Set
Module
Ok
Next
Page down
Converter
Address Lock
CCM03
To RS485/RS232
(F1,F2,E)
Converter
Installation
Outdoor Unit
(Master)
(X,Y,E)
(H1,H2,E)
(K1,K2,E)
(P,Q,E)
(P,Q,E)
(K1,K2,E)
Indoor Unit
Outdoor Unit
(Master)
(H1,H2,E)
(K1,K2,E)
(K1,K2,E)
(P,Q,E)
(P,Q,E)
(X,Y,E)
(X,Y,E)
Indoor Unit
Outdoor Unit
Outdoor Unit
(Slave)
(Slave)
(H1,H2,E)
(K1,K2,E)
(P,Q,E)
Indoor Unit
Indoor Unit
Outdoor Unit
Outdoor Unit
(Slave)
(Slave)
(H1,H2,E)
(K1,K2,E)
(P,Q,E)
(X,Y,E)
Indoor Unit
Indoor Unit
R410a DC Inverter 60Hz
Outdoor Unit
(Slave)
(H1,H2,E)
(K1,K2,E)
P
(P,Q,E)
Q
Max.64
Indoor Unit
Outdoor Unit
(Slave)
(H1,H2,E)
(K1,K2,E)
P
Max.64
Q
(P,Q,E)
(X,Y,E)
Indoor Unit
149