R410a DC Inverter 60Hz

4. Electric Characteristics

Model
38VF008H117010
38VF010H117010
38VF012H117010
38VF014H117010
38VF016H117010
38VF018H117010
The current value of combination unit is the total value of each basic model(refer to Units Combination Table in Part1)
For example: 46HP=14HP+16HP×2
Power current: MCA=54.6+54.6×2=163.8
TOCA=54.4+54.4×2=163.2
MFA=60+60×2=180
Compressor: RLA=(35.5+21.1)×3=169.8
OFM:
FLA=3.4×2+3.4×2×2=20.4
Remark:
MCA: Min. Current Amps. (A)
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
MSC: Max. Starting Amps. (A)
RLA: Rated Locked Amps. (A)
OFM: Outdoor Fan Motor.
FLA: Full Load Amps. (A)
KW: Rated Motor Output (KW)
Notes:
1. RLA is based on the following conditions, Indoor temperature 80.6℉(27℃) DB/66.2℉(19℃) WB,Outdoor temperature
95℉(35℃) DB
2. TOCA means the total value of each OC set.
3. MSC means the Max. current during the starting of compressor.
4. Voltage range. Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
5. Maximum allowable voltage variation between phases is 2%
6. Selection wire size based on the larger value of MCA or TOCA
7. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth circuit breaker).
26
Outdoor Unit
Hz
Voltage
Min.
Max.
60
208-230
188
253
60
208-230
188
253
60
208-230
188
253
60
208-230
188
253
60
208-230
188
253
60
208-230
188
253
Power Supply
Compressor
MCA
TOCA
MFA
MSC
36
35
40
-
36
35
40
-
46.5
49.5
55
-
54.6
54.4
60
-
54.6
54.4
60
-
65
73
85
-
Carrier service manual
OFM
RLA
KW
FLA
35.5
0.42
4.4
35.5
0.42
4.4
35.5+21.1
0.22×2
2.2×2
35.5+21.1
0.36×2
3.4×2
35.5+21.1
0.36×2
3.4×2
-
0.391×2
3.4×2
Specification & Performance