R410A DC Inverter Series
Carrier service manual
2.3 Dial codes definition
S1: starting up time setting
Starting time is set about 10 minutes
Starting time is set about 12 minutes(default)
S2: night silent time selection
Night time selection is
Night time selection is
Night time selection is
Night time selection is
6h/10h(default)
8h/10h
6h/12h
8h/12h
S3: silent mode selection
Night silent mode
Silent mode
Super silent mode
None silent mode
(default the factory set)
S4: ODU static pressure selection
Static pressure mode
Static pressure mode is
Static pressure mode is
Static pressure mode is
is low pressure
medium pressure (reserve
high pressure (reserve
0MPa (default)
(reserve position, use
position, use for
position, use for
for customized unit)
customized unit)
customized unit)
S5: locking modes selection
Heating priority
Cooling priority
VIP priority or Vote
Only respond to the
Only respond to the
mode(default)
mode
priority
heating mode
cooling mode
S6: addressing type selection
Nonautomatic search address
Clean the indoor unit addresses
(the communication way of the
(effective to automatic searching
Automatic search addressing
original digital indoor units)
new
(default)
digital indoor units)
S7 definition
S7
S7
ON
ON
1 2 3
1 2 3
Without setting the numbers of indoor
Need to set the numbers of indoor units
units(default)
S8 : reserved
160
Troubleshooting