Attached table 2:
Resistance value of compressor discharge temperature sensor
Temperature
Resistance
value (kΩ)
(℃)
-20
542.7
-19
511.9
-18
483
-17
455.9
-16
430.5
406.7
-15
-14
384.3
363.3
-13
-12
343.6
-11
325.1
-10
307.7
-9
291.3
-8
275.9
-7
261.4
-6
247.8
-5
234.9
-4
222.8
-3
211.4
200.7
-2
-1
190.5
180.9
0
1
171.9
2
163.3
3
155.2
4
147.6
5
140.4
6
133.5
7
127.1
8
121
115.2
9
10
109.8
104.6
11
12
99.69
95.05
13
14
90.66
86.49
15
16
82.54
78.79
17
18
75.24
71.86
19
Troubleshooting
Temperature
Resistance
value (kΩ)
(℃)
20
68.66
21
65.62
22
62.73
23
59.98
24
57.37
54.89
25
26
52.53
50.28
27
28
48.14
29
46.11
30
44.17
31
42.33
32
40.57
33
38.89
34
37.3
35
35.78
36
34.32
37
32.94
31.62
38
39
30.36
29.15
40
41
28
42
26.9
43
25.86
44
24.85
45
23.89
46
22.89
47
22.1
48
21.26
20.46
49
50
19.69
18.96
51
52
18.26
17.58
53
54
16.94
16.32
55
56
15.73
15.16
57
58
14.62
14.09
59
Temperature
Resistance
value (kΩ)
(℃)
60
13.59
61
13.11
62
12.65
63
12.21
64
11.79
11.38
65
66
10.99
10.61
67
68
10.25
69
9.902
70
9.569
71
9.248
72
8.94
73
8.643
74
8.358
75
8.084
76
7.82
77
7.566
7.321
78
79
7.086
6.859
80
81
6.641
82
6.43
83
6.228
84
6.033
85
5.844
86
5.663
87
5.488
88
5.32
5.157
89
90
5
4.849
91
92
4.703
4.562
93
94
4.426
4.294
95
96
4.167
4.045
97
98
3.927
3.812
99
R410A DC Inverter Series
Temperature
Resistance
value (kΩ)
(℃)
100
3.702
101
3.595
102
3.492
103
3.392
104
3.296
3.203
105
106
3.113
3.025
107
108
2.941
109
2.86
110
2.781
111
2.704
112
2.63
113
2.559
114
2.489
115
2.422
116
2.357
117
2.294
2.233
118
119
2.174
2.117
120
121
2.061
122
2.007
123
1.955
124
1.905
125
1.856
126
1.808
127
1.762
128
1.717
1.674
129
130
1.632
B(25/50)=3950K
R(90℃)=5KΩ±3%