15. CONTROLS - OPTIONAL ELEMENTS

TS
3-step regulator with built-in thermostat
Temperature setting range: +10 ... +30
Operating temperature range: 0 ... +40
Protection degree: IP30
Contact load: inductive: 5 A
Supply voltage: 230 V/50 Hz
FAN AUTO - fan operation depends on the
temperature.
FAN CONT - continuous fan operation
HEAT - heating function
FAN - deactivate the thermostat for FAN CONT
COOL - reversal of the operation logic of the
thermostat
T-box + DRV Slim (BMS possibility)
T-box + DRV Slim - touch screen controller +
control system
T-box:
Temperature setting range: +5 ... + 35
temperature range: -10 ... + 60
o
C Protection degree:
IP30
Supply voltage: 24 VDC
DRV Slim:
Operating temperature range: -10 ... + 60
Protection degree: IP54
Supply voltage: 230 V / 50 Hz
CONNECTION DIAGRAM IS IN DRV SLIM
DOCUMENTATION

16. ADJUSTMENT OF OUTLET GRILLE

PIC. 16.1 MANUAL ADJUSTMENT OF OUTLET GRILLE.
14
o
C
o
C
SCHEMAT 15.1. SLIM E + TS.
❶❷❸ The connection diagram for the remaining elements, along with a description of the
cables and protections, can be found in sections 12 and 13.
TS 3-step fan speed controller with thermostat TS (OMY min. 5x1,0 mm
o
C Operating
o
C
SCHEMAT 15.2. SLIM W/N + TS.
The device is equipped with two independently adjustable outlet
grilles. The angle should be set manually within +/- 5 °. The airflow
from the outlet grille should be directed as close as possible to the
plane of the door opening (taking into account the conditions
prevailing at the door opening).
ADVICE
In order to increase the effectiveness of the air barrier during windy
conditions, the curtain 's air stream should be directed outside the
door to create a more efficient air barrier to external factors.