13. BUILT-IN CONTROL – CONNECTION DIAGRAM SLIM E
PIC. 13.1 POWER SUPPLY 1N ~ 230V/50 Hz
❶ Power supply:
1N ~ 230V/50Hz:
SLIM E-100 (OMY min.3x1,5 mm
SLIM E-150 (OMY min.3x1,5 mm
SLIM E-200 (OMY min.3x2,5 mm
3N ~ 400V/50Hz:
SLIM E-100 (OMY min.5x2,5 mm
SLIM E-150 (OMY min.5x2,5 mm
SLIM E-200 (OMY min.5x4,0 mm
ADVICE
❸ Motion sensor; to omit/bypass the motion sensor; disconnect and insulate / secure wires from connectors D; D, a cable jumper
2
(OMY min. 1x1,0 mm
) or a door sensor (OMY min. 2x1,0 mm
❹ Heating switch ( I – heating elements ON , O – heating elements OFF);
❺ Fan step switch ( I – 1st fan step, O – device OFF, I I – 3rd fan step).
ADVICE
WARNING
12
2
; Protection B10)
2
; Protection B16)
2
; Protection B20)
2
; Protection B10)
2
; Protection B16)
2
; Protection B20)
-
The maximum outer diameter of the cable sleeve is 14.0 mm;
-
The minimum outer diameter of cable sleeve is 4.0 mm;
-
Maximum wire diameter 4,0 mm
To connect the 2nd fan step, connect the cable from the 6th connector to the 7th connector. In this case,
the I position on the switch will mean SWITCHING ON the 2nd fan step.
Each time the curtain is turned on by a motion sensor, it operates for a set time (10 s by default), unless
motion is detected in the area covered by the sensor.
In the event of a hazard arising from the unintentional reset of the thermal switch, this equipment should
not be powered by an external connecting device, such as a time switch, or a disconnector connected to
the circuit, which is regularly switched OFF and ON during use.
PIC. 13.2 POWER SUPPLY 3N ~ 400V/50 Hz
2
.
2
) should be connected in this place;