14. BUILT-IN CONTROL – CONNECTION DIAGRAM SLIM W; SLIM N
~
❶ Power supply: 1N
230V/50Hz (OMY min.3x1,5mm
❷ SRQ3d ½"; SRQ2d ½"
valve with actuator
ADVICE
-
The maximum outer diameter of the cable sleeve is 14.0 mm;
-
The minimum outer diameter of cable sleeve is 4.0 mm;
Maximum wire diameter 4,0 mm
❸ Motion sensor; to omit/bypass the motion sensor; disconnect and insulate / secure wires from connectors D; D, a cable jumper
2
(OMY min. 1x1,0 mm
) or a door sensor (OMY min. 2x1,0 mm
❹ Heating switch ( I – heating elements ON , O – heating elements OFF);
❺ Fan step switch ( I – 1st fan step, O – device OFF, I I – 3rd fan step).
ADVICE
WARNING
PARAMETRY ZAWORÓW SRQ:
- SRQ3d ½" – Three-way valve ½" with actuator
- SRQ2d ½" – Two-way valve ½" with actuator
2
; Protection B4)
(OMY min.3x0,75mm
2
.
To connect the 2nd fan step, connect the cable from the 6th connector to the 7th
connector. In this case, the I position on the switch will mean SWITCHING ON the 2nd
fan step.
Each time the curtain is turned on by a motion sensor, it operates for a set time (10 s by
default), unless motion is detected in the area covered by the sensor.
2
)
2
) should be connected in this place;
Class of protection: IP20
Supply voltage: 230/50 Hz
Max. Medium temperature: + 93oC Max. Operating pressure: 2.1Mpa
3
SRQ2d 1⁄2 "Kvs: 3.0 m
/h
3
SRQ3d 1⁄2 "Kvs: 3.4 m
/h
Motor running time: 18 s
A – Return pipe water supply
AB – Valve water supply
B – Exchanger water supply
13