Virtual Control - gefran GTF Configuration And Programming Manual

Power controller
Table of Contents

Advertisement

VIRTUAL INSTRUMENT CONTROL
Virtual instrument control is activated by means of parameter hd.1.
By setting parameter S.Io you can enable the writing of some parameters via serial line, set the value of
inputs and the state of outputs.
Enabling the PV input means being able to exclude the local Tc or RTD acquisition and replace it with the value written
in the register SERIAL_PV.
42
hd. 1
26
s. I o
Parameter
bit
S. lo
0
1
2
3
4
5
6
7
9
80961F_MSW_GTF/GTF-Xtra_07-2018_ENG
R/W
Type of operation
R/W
Control input/outputs from serial
Table of virtual register addresses
Resource enabled
Input PV
Input In.TA
Input In.TV
Input Digital
Output Out SSR
Output Out rL
Led 1
Led2
Output In.NTC
0 ... 1023
InNTC
-
Led 2
Bit
9
8
Address of
image register
132
133
134
131
131
131
131
131
135
Table type of operation
Led 1
Out rL Out SCR In Dig
7
6
5
4
3
Format
Name of register
Word
SERIAL_PV
Word
SERIAL_INTA
Word
SERIAL_INTV
Word bit 2
SERIAL_IO
Word bit 0
SERIAL_IO
Word bit 1
SERIAL_IO
Word bit 3
SERIAL_IO
Word bit 4
SERIAL_IO
Word
SERIAL_INNTC
0
0
inTV
inCT
PV
2
1
0
27