Electrical Specifications - Lindab WK45 Series Technical Manual

Patented fire damper
Hide thumbs Also See for WK45 Series:
Table of Contents

Advertisement

WK45
WK45
ELEC TRICAL CoNNEC TIoNS

Electrical specifications

Voltage and power consumption
Microswitches position contacts
Blade closing time
Protection degree
32/56
32/56
Manual
-
Manual control version:
15 - 400V
1,8 A
Spring: 1 s
IP42
Manual with magnet
Belimo motorized version
Siemens motorized version
Power interrruption magnet:
P=4,5 W (24V DC or 230 V AC version)
Motor 24V AC/DC (WK45VMB):
Belimo BFN24T
Opening: 4 W
In stand-by: 1,4 W
Motor 24V AC/DC (WK45VGB):
Belimo BF24T
Opening: 7 W
In stand-by: 2 W
Motor 24V AC/DC (WK45VPS) / (WK45VSS):
Siemens GNA126 / GRA126
Opening: 3,5 W
In stand-by: 2 W
Motor 24V AC/DC (WK45VGS):
Siemens GGA126
Opening: 6 W
In stand-by: 1.5 W
Motorized version:
Siemens: AC 24V...230V / 6 (2) A
Belimo: DC 5V...AC 250V / 1mA...3A (0,5A)
motor: < 30 s
IP42 MAGNETIC VERSION
IP54 MOTORIZED VERSION
Power input magnet:
P=4,5 W (24V DC or 230 V AC version)
Motor 230V AC (WK45DMB):
Belimo BFN230T
Opening: 5 W
In stand-by: 2,1 W
Motor 230V AC (WK45DGB)
Belimo BF230T
Opening: 8 W
In stand-by: 3 W
Motor 230V AC (WK45DPS) / (WK45DSS):
Siemens GNA326 / GRA326
Opening: 4,5 W
In stand-by: 3,5 W
Motor 230V AC (WK45DGS):
Siemens GGA326
Opening: 6 W
In stand-by: 2,5 W