Electrical Connections - Lindab WH25 Installation Booklet

Circular series - 500 pa fire damper
Hide thumbs Also See for WH25:

Advertisement

Installation remote from construction support
EI 120 S Installation remote from the vertical rigid wall
Wall minimum thickness 100 mm
Wall minimum density 550 kg/m³
Mortar or plaster putty sealing
ve (i↔o)
EI 120 S Installation remote from the vertical rigid wall with Fire Batt (Weichschott) sealing
Wall minimum thickness 100 mm
Wall minimum density 550 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i↔o)
EI 120 S Installation remote from the vertical light wall (plasterboard)
Wall minimum thickness 100 mm
Wall rock wool density up to 100 kg/m³ (optional)
Plasterboard and rock wool 100 kg/m³ or mortar or plaster putty
sealing
ve (i↔o)
EI 120 S Installation remote from the vertical light wall (plasterboard) with Fire Batt (Weichschott) sealing
Wall minimum thickness 100 mm
Wall rock wool density up to 100 kg/m³ (optional)
Rock wool density 140 kg/m³ and endothermic varnish sealing
ve (i↔o)
EI 120 S Installation remote from the vertical light wall (gypsum blocks wall)
Wall minimum thickness 100 mm
Wall minimum density 995 kg/m³
Mortar or plaster putty sealing
ve (i↔o)
EI 120 S Installation remote from the vertical light wall (gypsum blocks wall) with Fire Batt (Weichschott) sealing
Wall minimum thickness 100 mm
Wall minimum density 995 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i↔o)
EI 120 S Installation remote from the floor
Floor minimum thickness 150 mm
Floor minimum density 650 kg/m³
Mortar or plaster putty sealing
ho (i↔o)
EI 90 S Installation remote from the floor
Floor minimum thickness 100 mm
Floor minimum density 650 kg/m³
Mortar or plaster putty sealing
ho (i↔o)
Installations within vertical light wall (Shaft wall)
EI 90 S Installation within vertical light wall (Shaft wall)
Wall minimum thickness 90 mm
Plasterboard and mortar or plaster putty sealing
ve (i↔o)
ELEC TRICAL CONNEC TIONS
Electrical wiring
Electrical connections must be done by qualified and trained people.
Switch off the power supply before starting any work on the electric
elements. Never switch on the power supply during electrical con-
nections.
6/23
EI 120 S
(300 Pa)
Ø
W
min 100
max 315
Ø
D
min 100
max 315
Ø
D/W
min 100
max 315
Ø
D
min 100
max 315
Ø
W
min 100
max 315
Ø
D
min 100
max 315
Ø
W
min 100
max 315
W
-
W
EI 90 S
EI 60 S
(500 Pa)
(500 Pa)
Ø
Ø
min 100
min 100
max 315
max 315
Ø
Ø
min 100
min 100
max 315
max 315
Ø
Ø
min 100
min 100
max 315
max 315
Ø
Ø
min 100
min 100
max 315
max 315
Ø
Ø
min 100
min 100
max 315
max 315
Ø
Ø
min 100
min 100
max 315
max 315
Ø
Ø
min 100
min 100
max 315
max 315
Ø
Ø
min 100
min 100
max 315
max 315
EI 90 S
EI 60 S
(300 Pa)
(300 Pa)
Ø
Ø
min 100
min 100
max 315
max 315
EI 30 S
(500 Pa)
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
EI 30 S
(300 Pa)
Ø
min 100
max 315