Electrical Connections - Lindab FBC2 Installation Booklet

Advertisement

S
Smoke seal
Cert. N° FBC2 1812-CPR-1631,FBC5 1812-CPR-1633,FBC8 1812-CPR-1635
Fire Batt (Weichschott) sealings
Model FBC2 - FBC5 - FBC8: square hole, Weichschott sealing
Wall minimum thickness 100 mm
Wall minimum density 550 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i↔o)
Model FBC2 - FBC5 - FBC8: square hole, Weichschott sealing
Wall minimum thickness 100 mm
Wall rock wool density according to fire resistance class of
the wall
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i↔o)
Model FBC2 - FBC5 - FBC8: square hole, Weichschott sealing
Floor minimum thickness 150 mm
Floor minimum density 550 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ho (i↔o)
Floor minimum thickness 100 mm
Floor minimum density 550 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ho (i↔o)
W
Wet method sealing
D
Dry method sealing
ve
Vertical installation
ho
Horizontal installation
(i↔o) Origin of fire irrelevant
Pa
Pascal of depression
E
Integrity
I
Thermal insulation
S
Smoke seal
Cert. N° FBC2 1812-CPR-1631,FBC5 1812-CPR-1633,FBC8 1812-CPR-1635
Mechanism type
Manual
Blade closing mode
Automatic closing with thermal fuse.
The control mechanism has a thermosensitive element that automa-
tically closes the blade when the temperature in the duct exceeds
70°C.
The damper can be closed manually as per the following instructions.
The fire damper is equipped with a spring for closing the blade: pay
attention to the hands.
Blade opening mode
Make sure that the damper is open before the ventilation system
start-up, otherwise there is a risk of product malfunction.
In case of closed damper as a result of the action of the thermosensi-
tive element, it is possible to manually reopen the damper once the
thermosensitive element has been replaced.
The fire damper can be opened manually as per the following in-
structions.
The fire damper is equipped with a spring for closing the blade: pay
attention to the hands.
4/12
4
EI 120 S
(300 Pa)
W
FBC8
W
FBC8
W
FBC8
W
Position indication microswitch
On request, the fire damper can be supplied with position microswi-
tch (S1 optional) that signal the closed position of the blade. Refer to
the section Electrical connections for more details.
Temperature calibration of thermosensitive element for auto-
matic damper closing
70 °C±7 °C
Closing by remote control
Not available
Motorized version
Not available
ELEC TRICAL CONNEC TIONS
Electrical wiring
Electrical connections must be done by qualified and trained people.
Switch off the power supply before starting any work on the electric
elements. Never switch on the power supply during electrical con-
nections.
We reserve the right to make changes without prior notice
rev 20-10
EI 90 S
(300 Pa)
FBC8
FBC5
FBC8
FBC5
FBC8
FBC5
FBC8
-
FBC5
EI 60 S
EI 30 S
(300 Pa)
(300 Pa)
FBC8
FBC8
FBC5
FBC5
FBC2
FBC2
FBC8
FBC8
FBC5
FBC5
FBC2
FBC2
FBC8
FBC8
FBC5
FBC5
FBC2
FBC2
FBC8
FBC8
FBC5
FBC5
FBC2
FBC2