Electrical Components, Wiring Diagrams - Lindab SDR-S Technical Manual

Smoke control damper
Table of Contents

Advertisement

lin da b | we s im pli f y co ns tr u c t io n
Smoke Control Damper

8. Electrical components, wiring diagrams

7.1.
Actuating mechanism
Connection cable has to have to minimal 2 minues fire resistance
Tab. 8.1.1. Actuator BELIMO BEN 24(-ST), BEN 230
Actuator BELIMO - 15Nm
Power voltage
Power consumption
- in operation
- in the end position
Dimensioning
Protection class
Degree of protection
Adjustment time for 95°
Ambient temperature
Storage temperature
Connection
- drive
- auxiliary switch
Fig. 8
Actuator BELIMO BEN 24(-ST)
Fig. 9
Actuator BELIMO BEN 230
24
6 VA (Imax8,2A @ 5ms)
Cable 1m, 3x0,75mm
Cable 1m, 6x0,75mm
(BEN 24-ST) with plug connectors
AC/DC 24V
AC 230V
Lindab reserves the right to make changes without prior notice
BEN 24(-ST)
AC/DC 24V
50/60Hz
3W
0,1W
III
IP54
<30s
-30°C ... +55°C
-40°C ... +80°C
2
2
Last modified: 2021-10-26
Rev: 2021-03-26
SDR-S
BEN 230
AC 230V
50/60Hz
4W
0,4W
7 VA (Imax4A @ 5ms)
II
Cable 1m, 3x0,75mm
2
Cable 1m, 6x0,75mm
2

Advertisement

Table of Contents