Electrical Specifications; Technical Data - Lindab WH45 Installation Booklet

Hide thumbs Also See for WH45:
Table of Contents

Advertisement

Electrical specifications

Voltage and power consumption
Microswitches position contacts
Blade closing time
Protection degree

TECHNICAL DATA

Dimension
Ø
S blade exposition
Lp
Ø
S blade exposition
Lp
Lp
Overlap length between fire damper and duct
6/14
6
Manual
-
Manual control version:
15 - 400V
1,8 A
Spring: 1 s
IP42
mm
200
mm
0
mm
45
mm
450
mm
0
mm
45
We reserve the right to make changes without prior notice
Manual with magnet
Belimo motorized version
Siemens motorized version
Power interrruption magnet:
P=4,5 W (24V DC or 230 V AC version)
Motor 24V AC/DC (WH45VMB):
Belimo BFN24T
Opening: 4 W
In stand-by: 1,4 W
24V AC/DC (WH45VGB) motor:
Belimo BF24T
Opening: 7 W
In stand-by: 2 W
Motor 24V AC/DC (WH45VPS) /
(WH45VSS):
Siemens GNA126 / GRA126
Opening: 3,5 W
In stand-by: 2 W
24V AC/DC motor (WH45VGS):
Siemens GGA126
Opening: 6 W
In stand-by: 1,5 W
Motorized version:
Siemens: AC 24V...230V / 6 (2) A
Belimo: DC 5V...AC 250V / 1mA...3A (0,5A)
motor: < 30 s
IP42 MAGNETIC VERSION
IP54 MOTORIZED VERSION
250
300
0
0
45
45
500
560
0
0
45
45
rev 20-10
Power input magnet:
P=4,5 W (24V DC or 230 V AC version)
Motor 230V AC (WH45DMB):
Belimo BFN230T
Opening: 5 W
In stand-by: 2,1 W
230V AC (WH45DGB) Motor:
Belimo BF230T
Opening: 8 W
In stand-by: 3 W
Motor 230V AC (WH45DPS) /
(WH45DSS):
Siemens GNA326 / GRA326
Opening: 4,5 W
In stand-by: 3,5 W
230V AC motor (WH45DGS):
Siemens GGA326
Opening: 6 W
In stand-by: 2,5 W
315
355
0
0
45
45
600
630
0
0
45
45
400
0
45
710
800
35
80
45
45

Advertisement