Operation Of Sts At Each Mbs Position - Eaton Matrix Telecom Inverter System Installation And Operation Manual

Table of Contents

Advertisement

Matrix Telecom Inverter System

Operation of STS at each MBS position

Mains Bypass (MBP)
Mains Static Switch (MSS)
62
Copyright © 2008-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-68D
Mains Bypass:
Load is powered through
the MBS by the Mains AC
STS can be removed from
the system
MBS can only be switched
to Mains Static Switch
position
SCR2 open, SCR1 and Back-
feed Relay closed
If SCR2 is short, the STS
will stay in off-line mode
Inverter Maintenance (MSS):
Mains AC powers the load
through the static switch
Inverters are on, but do not
provide load any power
Inverters can be removed
from the system, but the
static switch cannot
MBS can be switched from
to Mains Bypass or Normal
Operation position
SCR2 open, SCR1 and Back-
feed Relay closed
If SCR2 is short, the STS
will stay in off-line mode
February 2010