Wire Terminal Lugs; Bus Bars - Trane CenTraVac CDHF Series Installation, Operation And Maintenance Manual

With tracer adaptiview control
Hide thumbs Also See for CenTraVac CDHF Series:
Table of Contents

Advertisement

terminal wire lugs. Terminal clamps provide additional
surface area to minimize the possibility of improper
electrical connections.

Wire Terminal Lugs

N N O O T T I I C C E E
C C o o m m p p o o n n e e n n t t D D a a m m a a g g e e ! !
F F a a i i l l u u r r e e t t o o e e n n s s u u r r e e t t h h e e p p o o w w e e r r s s u u p p p p l l y y w w i i r r i i n n g g a a n n d d
o o u u t t p p u u t t t t o o m m o o t t o o r r w w i i r r i i n n g g a a r r e e c c o o n n n n e e c c t t e e d d t t o o t t h h e e
p p r r o o p p e e r r t t e e r r m m i i n n a a l l s s c c o o u u l l d d c c a a u u s s e e c c a a t t a a s s t t r r o o p p h h i i c c f f a a i i l l u u r r e e
o o f f t t h h e e s s t t a a r r t t e e r r a a n n d d / / o o r r m m o o t t o o r r . .
Wire terminal lugs must be field supplied.
Use field-provided, crimp-type wire terminal lugs
properly sized for the application.
N N o o t t e e : : Wire size ranges for the starter line and load-
side lugs are listed on the starter submittal
drawings supplied by the starter
manufacturer or Trane. Carefully review the
submitted wire lug sizes for compatibility
with the conductor sizes specified by the
electrical engineer or contractor.
On 4160V and below, a terminal clamp with a
3/8-in. (9.525-mm) bolt is provided on each motor
terminal stud; use the factory-supplied Belleville
washers on the wire lug connections. The following
figure illustrates the junction between a motor
terminal stud and terminal lug.
Torque for this assembly is 24 ft·lb (32.5 N·m).
Install but do NOT connect the power leads
between the starter and compressor motor. (These
connections will be completed under supervision of
a qualified Trane service engineer after the pre-start
inspection.)
CDHF-SVX01N-EN
Figure 44. Terminal stud, clamp, and lug assembly
(4160V and below)
4
5
1. Belleville washer
2. Terminal lugs
3. Terminal clamp
4. Motor terminal stud
5. 3/8-in. bolt

Bus Bars

N N O O T T I I C C E E
C C o o m m p p o o n n e e n n t t D D a a m m a a g g e e ! !
F F a a i i l l u u r r e e t t o o f f o o l l l l o o w w i i n n s s t t r r u u c c t t i i o o n n s s b b e e l l o o w w c c o o u u l l d d c c a a u u s s e e a a n n
e e l l e e c c t t r r i i c c a a l l s s h h o o r r t t w w h h i i c c h h c c o o u u l l d d r r e e s s u u l l t t i i n n c c o o m m p p o o n n e e n n t t
d d a a m m a a g g e e . .
R R e e m m o o v v e e d d e e b b r r i i s s f f r r o o m m i i n n s s i i d d e e t t h h e e C C P P T T R R o o p p t t i i o o n n
e e n n c c l l o o s s u u r r e e p p a a n n e e l l b b e e f f o o r r e e t t u u r r n n i i n n g g t t h h e e p p o o w w e e r r o o n n . .
Bus bars and extra nuts are available as a Trane option.
Install the bus bars between the motor terminals when
using a starter that is:
A low-voltage Adaptive Frequency™ Drive (AFD)
Across-the-line
Primary reactor/resistor
Autotransformer
Customer-supplied
Connect T1 to T6, T2 to T4, and T3 to T5.
N N o o t t e e : : Bus bars are not needed in medium-voltage or
high-voltage applications since only
three terminals are used in the motor and starter.
When attaching starter leads to 6.6 to 7kV motor
terminals, the 1/2-in.-13 brass jam nuts should be
tightened to a maximum torque of 18 to 22 ft·lb (24.4 to
29.8 N·m). Always use a second wrench to backup the
P P o o w w e e r r S S u u p p p p l l y y W W i i r r i i n n g g
2
1
3
59