I I n n s s u u l l a a t t i i o o n n
Figure 28. Recommended area for unit insulation
Line to eductor
Pipe
Economizer
Pipe
N N o o t t e e s s : :
•
Bulbwells, drain, and vent connections must be accessible after insulating.
•
All units with evaporator marine waterboxes: wrap waterbox shell insulation with strapping and secure
strapping with seal.
•
Evaporators with ASME nameplates must have insulation cut out around the nameplate. Do NOT glue
insulation to the nameplate.
•
Apply 2-in. (50.8-mm) wide black tape on overlap joints. Where possible, apply 3-in. (76.2-mm) wide strip of
0.38-in. (9.7-mm) thick insulation over butt joint seams.
•
Insulate all economizer supports.
42
Line from evaporator
Filter drier
and eductor lines
Suction
Suction
Control
connection
panel
support
Evaporator
See first
two notes
Suction
cover
elbow
See first
note
Eductor
line
CDHF-SVX01N-EN
See first
two notes