Trane-Supplied Starter Wiring - Trane CenTraVac CDHF Series Installation, Operation And Maintenance Manual

With tracer adaptiview control
Hide thumbs Also See for CenTraVac CDHF Series:
Table of Contents

Advertisement

W W A A R R N N I I N N G G
L L i i v v e e E E l l e e c c t t r r i i c c a a l l C C o o m m p p o o n n e e n n t t s s ! !
F F a a i i l l u u r r e e t t o o f f o o l l l l o o w w a a l l l l e e l l e e c c t t r r i i c c a a l l s s a a f f e e t t y y p p r r e e c c a a u u t t i i o o n n s s
w w h h e e n n e e x x p p o o s s e e d d t t o o l l i i v v e e e e l l e e c c t t r r i i c c a a l l c c o o m m p p o o n n e e n n t t s s c c o o u u l l d d
r r e e s s u u l l t t i i n n d d e e a a t t h h o o r r s s e e r r i i o o u u s s i i n n j j u u r r y y . .
W W h h e e n n i i t t i i s s n n e e c c e e s s s s a a r r y y t t o o w w o o r r k k w w i i t t h h l l i i v v e e e e l l e e c c t t r r i i c c a a l l
c c o o m m p p o o n n e e n n t t s s , , h h a a v v e e a a q q u u a a l l i i f f i i e e d d l l i i c c e e n n s s e e d d e e l l e e c c t t r r i i c c i i a a n n
o o r r o o t t h h e e r r i i n n d d i i v v i i d d u u a a l l w w h h o o h h a a s s b b e e e e n n p p r r o o p p e e r r l l y y t t r r a a i i n n e e d d
i i n n h h a a n n d d l l i i n n g g l l i i v v e e e e l l e e c c t t r r i i c c a a l l c c o o m m p p o o n n e e n n t t s s p p e e r r f f o o r r m m
t t h h e e s s e e t t a a s s k k s s . .
Table 15. Standard field power wiring requirements
Power Supply Wiring
to Starter Panel
3-Phase Line Voltage
3-Phase Line Voltage: Circuit Breaker
Starter to Motor Power Wiring
Remote Starter to Chiller Motor Junction Box
Starter to Control Panel
120 Vac Control Wiring
120 Vac Power Supply (from Starter to
Control Panel)
High Pressure Cutout to Starter
1Q1 Circuit Breaker to Starter
Oil Pump Interlock
Low Voltage Circuits
Less Than 30 Vac
Standard Circuits
Inter-processor Communications (IPC)
Remote-Mounted
Notes:
1.
All wiring to be in accordance with National Electrical Code (NEC) and any local codes.
2.
Oil pump motor: 1 Ph, 3/4 HP, 11.7 full load amps at 115 Vac.
3.
Auxiliary equipment must be powered from other sources as the chiller control panel power supplies are sized for the chiller loads only.
(a)
Ground lug for a unit-mounted solid state starter or wye-delta starter is sized to accept 14 AWG solid to 8 AWG strand wire. If local codes require different
lug size, it must be field-supplied and -installed.
(b)
Wires, lugs, and fuses/breakers are sized based on National Electric Code NEC [NFPA 70] and UL 1995.
1Q1 Circuit Breaker to Starter connects to 2X16 Starter Panel Terminal for all starter types except the AFDG (Trane-supplied remote Danfoss AFD); for the
(c)
AFDG, 1Q1 Circuit Breaker to Starter connects to 2X13 Starter Panel Terminal.
(d)
Must be separated from 120 Vac and higher wiring.
N N o o t t e e : : Control Power Transformer (CPTR, Enhanced
Electrical Protection Package option): A unit-
mounted, factory-wired, separate enclosure
positioned next to the control panel is available
when separate source control power is required.
This permits the controls to remain powered
while the three-phase line voltage is
disconnected. Contact your local Trane
representative for more information.
CDHF-SVX01N-EN
Starter Panel
Terminals
2X3-L1, L2, L3, and Ground
2Q1-L1, L2, L3, and Ground
Starter
T1 through T6
Starter Panel
Terminals
2X1-1, 2X1-2
2X1-20 (Ground)
2X1-4
2X1-7, 2X1-8
Starter Panel
Terminals
2A1-J3-3-4, or
2X1-12 to 13 if Present (Do
(d)
NOT Ground Shield at Starter)

Trane-supplied Starter Wiring

This information is applicable to Starter 1 for
Compressor 1 as well as Starter 2 for Compressor 2.
(For wire estimation purposes, double check the
following table as there are two starters to be wired.)
(a)
Motor
T1 through T6
Unit Control Panel
Terminations
1X1-1, 1X1-12
1X1-18 (Ground)
1X1-4
(c)
1X1-3
1A7-J2-4, 1A7-J2-2
Unit Control Panel
Terminations
1A1-J5-1-2, 3-4
Shield Ground at
1X1-22 (GND) Only
E E l l e e c c t t r r i i c c a a l l R R e e q q u u i i r r e e m m e e n n t t s s
Max Terminal Wire
Minimum Circuit
Size (AWG)
Ampacity
(b)
8
14
14
14
2-wire with Gound
Comm Link
40
20
20
20
53