Trane CenTraVac CDHF Series Installation, Operation And Maintenance Manual page 11

With tracer adaptiview control
Hide thumbs Also See for CenTraVac CDHF Series:
Table of Contents

Advertisement

W W A A R R N N I I N N G G
C C o o m m b b u u s s t t i i b b l l e e M M a a t t e e r r i i a a l l ! !
F F a a i i l l u u r r e e t t o o f f o o l l l l o o w w i i n n s s t t r r u u c c t t i i o o n n s s b b e e l l o o w w c c o o u u l l d d r r e e s s u u l l t t i i n n
d d e e a a t t h h o o r r s s e e r r i i o o u u s s i i n n j j u u r r y y o o r r e e q q u u i i p p m m e e n n t t d d a a m m a a g g e e . .
S S h h r r i i n n k k - - w w r r a a p p i i s s a a c c o o m m b b u u s s t t i i b b l l e e m m a a t t e e r r i i a a l l . . A A v v o o i i d d o o p p e e n n
f f l l a a m m e e s s a a n n d d h h o o t t s s p p a a r r k k s s . .
Trane Supplied
Type of Requirement
Trane Installed
Foundation
Rigging
Disassembly/Reassembly
(as required)
Isolation
Electrical
CDHF-SVX01N-EN
Trane Supplied
Field Installed
Trane will perform or have
direct on-site supervision
of the disassembly and
reassembly work (contact
your local Trane office for
pricing)
Circuit breakers or fusible
disconnects (optional)
Unit-mounted starter
(optional)
Power factor correction
capacitors (PFCCs)
(optional)
N N o o t t e e : : The chiller should remain within its protective
shrink-wrap covering during storage.
Field Supplied
Field Installed
Meet foundation requirements
Safety chains
Rigging shackles
Lifting beam
Isolation pads or spring isolators
Optional spring isolators, when required, are
Isolation pads or spring
installed by others; do NOT overload springs and do
isolators
NOT install isolation springs if they block serviceable
parts such as the oil tank system, service valves,
etc.
Circuit breakers or fusible disconnects (optional)
Electrical connections to unit-mounted starter
(optional)
Electrical connections to remote-mounted starter
(optional)
Wiring sizes per submittal and National Electric Code
(NEC)
Jumper bars
PFCCs (remote mounted starter optional only)
Temperature sensor
Terminal lugs
(optional outdoor air)
Ground connection(s)
Flow switches (may be
field supplied); for
Jumper bars
installation instructions
BAS wiring (optional)
for the ifm efector®
flow detection controller
Inter-processor communication (IPC) wiring (AFD
and sensor, refer to
and remote-mounted starters only)
"Water Flow Detection
Control voltage wiring (AFD and remote-mounted
Controller and
starters only)
Sensor," p. 25
or Trane
literature that shipped
Oil pump interlock wiring (AFD and remote mounted
with the device
starters only)
Remote-mounted
High condenser pressure interlock wiring (AFD and
starter (optional)
remote-mounted starters only)
Chilled water pump contactor and wiring including
interlock
Condenser water pump contactor and wiring
including interlock
Option relays and wiring
Tracer® SC communication wiring (optional)
P P r r e e - - I I n n s s t t a a l l l l a a t t i i o o n n
11