Recommended Wire Lengths For Pts - Trane CVHE Troubleshooting Manual

Table of Contents

Advertisement

The maximum recommended wire length for PT leads in a dual PT system are:
Wire
Max Wire Length
Gauge
Primary (ft)
8
3061
9
2428
10
1924
11
1526
12
1211
13
960
14
761
15
603
16
478
17
379
18
301
19
238
20
189
21
150
22
119
Note: These wire lengths are for copper conductors only
Note: The above lengths are maximum round trip wire lengths. The maximum distance
the PT can be located is 1/2 of the listed value.
CVHE-SB-32A
Max Wire Length
Primary (m)
933
740
586
465
369
292
232
184
145
115
91
72
57
45
36
Max Wire Length
Secondary (ft)
711
564
447
355
281
223
177
140
111
88
70
55
44
34
27
Max Wire Length
Secondary (m)
217
172
136
108
85
68
53
42
33
26
21
16
13
10
8
106